The brightness of adjacent EMXs cannot be taken into account
Problem
If one of several EMX units ends up in the shadow cast by adjacent buildings depending on the sun’s position, but not all sectors on the building are affected by this shading, it must be possible to receive the highest brightness.
Workaround
Starting with SW Version 2.0 and Application 2.0, ComObject 247 can be used to receive the maximum brightness of a neighboring EMX. The maximum brightness of sensors 1 through 4 (north, east, south, west) and of ComObject 247 is output to ComObject 27. This maximum brightness is taken into account by the shading evaluation with the "central" setting.
Occurs in version
- .V1.6.V1.10
- 160.V1.7.V1.10
- 194.V1.8.V1.10
- 195.V1.9.V1.10
- 198.V1.10.V1.10
- 199.V1.10.V1.11
- 253.V1.10.V1.12
- 254.V1.11.V1.12
- 268.V1.11.V1.13
- 269.V1.21.V1.13
- 305.V1.22.V1.13