EMX-8: Griesser system with communication modules for conventional actuators

Created by Jean-Claude Hirzel, Modified on Wed, 25 Mar at 6:41 AM by Jean-Claude Hirzel

EMX-8 Griesser device with communication modules for conventional actuators



Problem

If the "Show communication objects for conventional actuators" flag is selected and the Griesser object is also assigned a group address, the Griesser object's button lock for this sector remains active after a lock.



Workaround

If "Communication objects for conventional actuators" is used, the Griesser object must not be used for this sector.

Occurs in version

  • .V1.6.V1.10
  • 160.V1.7.V1.10
  • 198.V1.10.V1.10
  • 199.V1.10.V1.11
  • 253.V1.10.V1.12
  • 254.V1.11.V1.12
  • 268.V1.11.V1.13
  • 269.V1.21.V1.13
  • 305.V1.22.V1.13
  • 328.V1.23.V2.0
  • 350.V1.24.V2.2
  • 367.V1.24.V2.0
  • 367.V1.25.V2.2
  • 372.V1.26.V2.2
  • 373.V1.27.V2.2
  • 376.V1.28.V