FS-4I: Addressing conflicts/errors in the Griesser LINK network; perform a system reset to resolve

Created by Jean-Claude Hirzel, Modified on Wed, 25 Mar at 6:45 AM by Jean-Claude Hirzel

Addressing conflicts/errors in the Griesser LINK network; perform a system reset to resolve



Problem

If Griesser LINK devices (Flexmodul, BGS, BGT, GTS) are configured using FlexTool without ALL Griesser LINK devices configured in FlexTool being in operation and connected via Griesser LINK, addressing conflicts may occur later during operation within the device network. Under certain circumstances, individual Griesser LINK devices may then not be addressable via the ID assigned by FlexTool. The products affected are Flexmodul, BGS, BGT, and GTS (all Griesser LINK devices except FUE, FG-4, and FlexTool); details.


Workaround

Perform a system reset to restart Griesser LINK devices that can process this command (broadcast).
If the problem cannot be resolved via a system reset, disconnect all Griesser LINK devices from the power supply and reconnect them while all devices remain connected to each other via Griesser LINK (see Bug RM003519).

To trigger a system reset:
- FlexModule and GTS: Press the LINK button until the LINK LED flashes rapidly (takes approx. 5 seconds), then release the LINK
button. - GTS additionally: Via web interface /setup, "System Reset" button
- BGT: Press the "Reset System" button

in the Service Menu Required software versions for triggering and processing the system reset
:- BGT: The "Reset System" button performs a reset of all FlexModules (Unicast) and, starting with SW V3.8, additionally triggers the Broadcast System Reset
- GTS: System reset starting with SW V2.2 (triggered with the LINK button only in normal operation (LED off); in "IP Factory Settings" mode (LED on), the system reset has no effect).
- FMX/gFM/FS-4I SW V1.20

Occurs in versions

  • V1.3.V1.17
  • 327.V1.3.V1.19

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article