Device downloads fail if multiple devices on the GriesserLINK have the same ID
Problem
When attempting to configure a device via FlexTool Remote, FlexTool aborts the process with the message "Read NOK." Configuration does not take place.
This problem can occur if there are multiple devices with the same ID on the GriesserLINK. In this case, FlexTool Remote cannot uniquely identify the recipient of the configuration—even when the programming button is held down.
Workaround
Ensure that the GTS has the correct ID. If in doubt, reload the GTS configuration. If this
does not resolve the issue, load the correct configuration into the devices via the USB-GriesserLINK adapter (FTDUS).
Occurs in version
- .V1.2.V2.1
- 127.V1.2.V2.2
- 352.V1.3.V2.2
- 353.V1.3.V2.1
- 353.V1.4.V2.2