FMX: Sector status does not display local operation via BGS, BGT, GTS, or Flexmodule

Created by Jean-Claude Hirzel, Modified on Wed, 25 Mar at 6:44 AM by Jean-Claude Hirzel

The sector status is not displayed when using local controls via BGS, BGT, GTS, or the Flex module 



Problem

Conceptual Background:
FlexModules store only central commands in their sector states, not local commands.
In particular, FlexModules use the command stored in the sector state to repeat the last central command.
Local commands include both manual operations on the actuator (which are not recognized by the control center at all) and commands from control sources at the Griesser Link level (BGS, BGT, GTS, FlexModule contact inputs) that are configured as "Local" and are therefore treated in the same way as a "genuine" local command directly at the actuator.


Workaround

- Check the logging for the execution of
local commands at the Griesser Link level. - Configure commands at the Griesser Link level as central commands so that they are displayed in the visualization.

Occurs in version

  • .1.0.1.18
  • .1.2.1.18
  • .1.4.1.18
  • .V1.4.V1.17
  • 129.V1.x.V1.18
  • 298.V1.x.V1.19
  • 307.1.1.1.18
  • 308.1.1.1.18
  • 309.1.5.1.18
  • 310.1.3.1.18
  • 312.1.1.1.19
  • 313.1.1.1.19
  • 314.1.5.1.19
  • 315.1.3.1.19
  • 326.V1.x.V1.20
  • 330.1.3.1.20
  • 331.1.1.1.20
  • 332.1.1.1.20
  • 333.1.5

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article