The sector status is not displayed when using local controls via BGS, BGT, GTS, or the Flex module
Problem
Conceptual Background:
FlexModules store only central commands in their sector states, not local commands.
In particular, FlexModules use the command stored in the sector state to repeat the last central command.
Local commands include both manual operations on the actuator (which are not recognized by the control center at all) and commands from control sources at the Griesser Link level (BGS, BGT, GTS, FlexModule contact inputs) that are configured as "Local" and are therefore treated in the same way as a "genuine" local command directly at the actuator.
Workaround
- Check the logging for the execution of
local commands at the Griesser Link level. - Configure commands at the Griesser Link level as central commands so that they are displayed in the visualization.
Occurs in version
- .1.0.1.18
- .1.2.1.18
- .1.4.1.18
- .V1.4.V1.17
- 129.V1.x.V1.18
- 298.V1.x.V1.19
- 307.1.1.1.18
- 308.1.1.1.18
- 309.1.5.1.18
- 310.1.3.1.18
- 312.1.1.1.19
- 313.1.1.1.19
- 314.1.5.1.19
- 315.1.3.1.19
- 326.V1.x.V1.20
- 330.1.3.1.20
- 331.1.1.1.20
- 332.1.1.1.20
- 333.1.5