Problem
If, after configuring the project, the "Sensor" column in an automation program still shows "no sensor," this is correctly identified by the project plausibility check as a missing sensor assignment.
However, if a suitable bus sensor is assigned to an automation program but is subsequently defined as a different type in the KNX Sensors tab (BUS Sensor - Receive) and therefore no longer matches the automation type, this sensor is hidden in the Sensor column of the automation program (field empty -> no sensor assigned).
Unfortunately, this lost sensor assignment is not detected by the plausibility check.
Workaround
The FT plausibility check does not exempt you from a comprehensive functional test during commissioning
Occurs in version
- .V1.12.V5.3
- 125.V1.13.V5.4