GTS: IP cannot be changed

Created by Jean-Claude Hirzel, Modified on Wed, 25 Mar at 6:49 AM by Jean-Claude Hirzel

The GTS IP address cannot be changed



Problem

The IP address of the RFM, GTS cannot be changed.
The default setting 192.168.0.8 cannot be overwritten.



Workaround

If an invalid combination of IP, subnet mask, and default gateway is specified in the Flex Tool, the RFM and GTS will start with the default IP settings.

If the subnet mask is 255.255.255.255, the configuration is invalid.

A combination can be checked as follows: If a digit in the subnet mask is 255, the corresponding digit in the IP address and the default gateway must be the same. For digits other than 255, the following check can be performed using the Windows Calculator in "Programmer" mode: The value of
"<IP digit> AND <subnet mask digit>" must be equal to the value of "<default gateway digit> AND <subnet mask digit>".


Occurs in version

  • .V1.0.V1.0
  • 131.V1.0.V1.1
  • 188.V1.1.V1.1
  • 189.V1.1.V2.1

Was this article helpful?