FMX: After falling below or exceeding the brightness threshold, the brightness command is issued again

Created by Jean-Claude Hirzel, Modified on Wed, 25 Mar at 6:44 AM by Jean-Claude Hirzel

If the brightness falls below or exceeds the threshold, the brightness control command is issued again



Problem

If the switch-off delay has not yet elapsed, the "On_active" state is maintained. When light, no light state is generated, and consequently no light drive command is issued. If no switch-off time is stored for VZDP, a drive command is issued randomly or not at all, but the Off state (Off_active) is reached immediately. When it is light, a drive command is issued again, which is therefore difficult to understand.



Workaround

VZDP1=VZDP2 should be greater than Dark1=Dark2.

Occurs in version

  • 129.V1.x.V1.18
  • 298.V1.x.V1.19
  • 326.V1.x.V1.20