Duplicate communication objects in DCA mode
Problem
There may be cases where communication objects (CO) exist in duplicate in DCA mode. However, only one of these COs is connected to the DCA at any given time.
To determine which CO is connected, you can view the CO number on the corresponding tile under Communication Objects.
Workaround
The DCA must be updated to version 2.0 or higher, and the device must be opened with the DCA. This will remove the "orphaned"
duplicate communication objects. The "Update Configuration" dialog does not need to be confirmed. To repair multiple devices, simply open them in the DCA Toolbox.
Occurs in version
- 380.1.X.1.X