EasyTec: Setting Threshold Values in EasyTec

Created by Jean-Claude Hirzel, Modified on Wed, 25 Mar at 6:53 AM by Jean-Claude Hirzel

Setting Thresholds in EasyTec



Problem

To precisely set limit values (brightness, wind), you need the following
:- SIMU-G (Griesser sensor simulator)
- EKB (control unit)
- SIMU-VBK adapter cable (013097.511)
(- EasyTec control panel)



Procedure
:- Turn the threshold potentiometer to max. (brightness 40 / wind 100)
-
Connect the SIMU-G to the control unit using the SIMU-VBK- Connect the EKB to the
control unit- Display the sensor value to be set on the EKB (e.g., actual wind value)
- Set the desired value on the SIMU-G (display on EKB, e.g., wind 50 km/h)
- Turn the threshold potentiometer on the FMT back until the LED indicator changes from red
to green- The exact threshold value (e.g., wind alarm exactly at 50 km/h) is now set

Occurs in version

  • 1.7.3.38
  • 149.1.8.3.38
  • 150.1.9.3.38